3-Phase Load Calculator

Line-to-line voltage.

Phase Loads (kW or kVA)

Average PF for all phases.

Complete Guide to 3-Phase Load Calculation

The 3-Phase Load Calculator computes total kW, kVA, current, and balance. Detects imbalance >10%. Our free tool ensures NEC compliance and system reliability.

What is 3-Phase Load?

Three-phase power: P = √3 × V × I × PF. Balanced = equal per phase. Our 3-Phase Load Calculator handles unbalanced loads.

Why Balance Loads?

Benefits:

  • Lower Neutral Current: Reduce heating.
  • Transformer Life: Avoid derating.
  • Compliance: NEC 310.15(B)(5).
  • Efficiency: Less loss.

Use with Neutral Current and Load Balance.

3-Phase Formulas

  • Total kW = A + B + C
  • kVA = kW / PF
  • Current = kVA × 1000 / (√3 × V)
  • Imbalance % = (Max - Min) / Avg × 100

Load Types

TypeTypical PFPhase
Resistive (Heaters)1.0Any
Inductive (Motors)0.8Line-to-line
Lighting0.95Line-to-neutral
Receptacles0.9Line-to-neutral

Imbalance Limits

ComponentMax Imbalance
Transformer10%
Panelboard20%
Neutral100% of phase

Calculation Steps

  1. Measure: kW per phase.
  2. Sum: Total kW.
  3. Apply PF: kVA.
  4. Current: I = kVA × 1000 / (√3 × V)
  5. Check Balance: <10%.

Example: Factory Panel

480V, Phase A: 50 kW, B: 60 kW, C: 40 kW, PF 0.85.

  • Total kW = 150 kW
  • kVA = 150 / 0.85 = 176.5 kVA
  • I = 176.5 × 1000 / (1.732 × 480) = 212 A
  • Imbalance = (60-40)/50 × 100 = 40% → Unbalanced!

How to Balance

  • Redistribute: Single-phase loads.
  • Use 3-Phase: Motors, HVAC.
  • Monitor: CTs, meters.
  • Auto Transfer: Load management.

Practical Applications

For:

  • Factories: Motors, welders.
  • Commercial: Lighting, receptacles.
  • Data Centers: Servers.
  • EV Stations: Charging.

Tips

  • Measure PF: Per phase if different.
  • Derate: >10% imbalance.
  • Neutral Sizing: 200% if nonlinear.
  • Log Data: Trend imbalance.

Common Mistakes

  • Assume Balance: Without measuring.
  • Ignore PF: Wrong kVA.
  • Wrong Voltage: L-N vs L-L.
  • No Spare: Future loads.

Advanced Topics

  • Vector Sum: For currents.
  • Harmonics: 3rd in neutral.
  • Power Quality: Voltage unbalance.
  • NEMA MG-1: Motor derating.

Conclusion

Balanced 3-phase loads improve efficiency and equipment life. Our 3-Phase Load Calculator instantly flags imbalance. Combine with Neutral Current and Construction tools. Optimize with 1000 Calculators.