Conduit Fill Calculator

NEC Table 4. All 40% fill over 2 wires.

Wire Configuration

Complete Guide to Conduit Fill

The Conduit Fill Calculator ensures ≤40% fill per NEC Chapter 9. Prevents jamming, heat, and code violations.

What is Conduit Fill?

% fill = (total wire area / conduit area) × 100. Max: 53% (1 wire), 31% (2), 40% (>2). Our Conduit Fill Calculator uses Annex C.

Why Limit Fill?

Avoids:

  • Jamming: Wire damage during pull.
  • Overheating: Reduced dissipation.
  • Code Violation: Inspector rejection.
  • Pull Difficulty: High friction.

Use with Wire Size and Derating.

NEC Fill Rules (Chapter 9)

WiresMax % Fill
153%
231%
≥340%

Conduit Types

NEC Table 4 dimensions:

  • EMT: Most common.
  • RMC: Rigid metal.
  • PVC: Sch 40/80.
  • FMC: Flexible.

Wire Area (Annex C)

THHN/THWN (in²):

AWGArea
140.0133
120.0157
100.0211
80.0366
60.0507
40.0824

Calculation Steps

  1. Select: Conduit type & size.
  2. Add: Wire AWG + count.
  3. Compute: Total wire area.
  4. Check: ≤40% (or 31%/53%).

Example: 3/4" EMT

6× #12 THHN + 4× #10 THHN.

  • Area: 6×0.0157 + 4×0.0211 = 0.1784 in²
  • EMT area: 0.533 in²
  • Fill: 33.5% → OK

Max Wires (Annex C)

THHN in 1" EMT:

AWGMax Count
1434
1226
1019
811

Mixed Sizes

Allowed. Calculator sums areas.

Practical Tips

  • Derate: >3 current-carrying → 80%.
  • Pull Box: Every 360° bend.
  • Lube: Reduce friction.
  • Oval: Not circular → measure.

Common Mistakes

  • Ignore Insulation: Use THHN area.
  • Wrong Table: EMT ≠ PVC.
  • Count Grounds: Yes, all wires.
  • Forget Nipples: 60% fill <24".

Advanced

  • Jam Ratio: 2.8–3.2 → risk.
  • Pull Tension: Software.
  • Compact Stranding: Smaller area.
  • Fiber Optic: Different rules.

Conclusion

Proper fill prevents damage and ensures compliance. Our Conduit Fill Calculator uses NEC Annex C. Pair with Wire Size and Construction tools. Build safe with 1000 Calculators.