Harmonic Distortion Calculator

V-THD ≤ 5%, I-THD per IEEE 519.

V1 or I1 in volts/amps.

Harmonic Magnitudes

Complete Guide to Harmonic Distortion

The Harmonic Distortion Calculator computes THD (%) for voltage and current. Ensures IEEE 519 compliance.

What is THD?

THD = √(Σ H₂²…Hₙ²) / H₁ × 100%. Our Harmonic Distortion Calculator supports up to 50th order.

Why Control Harmonics?

Causes:

  • Overheating: Transformers, cables.
  • Tripped Breakers: False trips.
  • Neutral Overload: 3rd harmonics.
  • Equipment Damage: Motors, drives.

Use with Neutral Current and Transformer Size.

IEEE 519 Limits

ParameterLimit
V-THD≤ 5%
I-THD (ISC/IL < 20)≤ 5%
I-THD (20–50)≤ 8%
I-THD (>1000)≤ 15%

Common Sources

LoadTypical THD
PCs70–100%
LED Lights15–40%
VFDs30–50%
UPS5–15%

Calculation Formula

THD = √(V₂² + V₃² + … + V₅₀²) / V₁ × 100

Example: Office Panel

V1 = 480V, V3 = 12V, V5 = 8V, V7 = 5V.

  • Σ H² = 12² + 8² + 5² = 233
  • √233 = 15.26
  • THD = 15.26 / 480 × 100 = 3.18% → PASS

Mitigation

  • Filters: Passive/active.
  • K-Rated Transformers: Handle heat.
  • Phase Shifting: Cancel 5th/7th.
  • Line Reactors: Reduce I-THD.

Measurement

  • True-RMS Meter: With FFT.
  • Power Analyzer: Fluke 435.
  • Up to 50th: IEEE requirement.

Practical Tips

  • Separate Neutrals: Per phase.
  • Oversize Neutral: 200% if >50% nonlinear.
  • Monitor PCC: Point of common coupling.
  • Derate Transformers: K-factor.

Common Mistakes

  • Average Meter: Wrong THD.
  • Ignore 3rd: Neutral burn.
  • No ISC/IL: Wrong I-THD limit.
  • Single Phase: Miss triplen.

Advanced

  • TDD: Total Demand Distortion.
  • K-Factor: Transformer rating.
  • Crest Factor: Peak/RMS.
  • Interharmonics: Non-integer.

Conclusion

Harmonics degrade power quality. Our Harmonic Distortion Calculator ensures IEEE 519 compliance. Pair with Neutral Current and Construction tools. Stay efficient with 1000 Calculators.